Opened, Stopped and Unplugged Machine
OPENED, STOPPED AND UNPLUGGED MACHINE
-
Measure partial discharge off-line
-
Measure insulation resistance i.r
according to UQ602011C standard -
Determine polarization index i.p.
according to ieee std 43-2000 standard -
Measure tangent of loss angle tan δ in winding insulation and its variation in δ tan δ
based on voltage: 0.2 – 0.4 – 0.6 – 0.8 –rated voltage -
Measure μf winding of electrical windings respect to the mass, compared with same voltage
present in the previous point test ground voltage
according to UQ602010C standard -
Test balance of phases through ohmic resistance
according to UQ602012C standard -
Test balance of phases through impedance z ohm
according to ieee std 56-1977 standard -
Check up motor space heaters and thermoelements
-
Check status of closures
-
Check status of keys
according to UQ602028C standard -
Check status of anti-effluvium protection
ROTOR OUT OF STATOR
-
Measure insulation resistance i.r
according to UQ602011C standard -
Check total static ohmic resistance and in every single pole
according to UQ602012C standard -
Check total static impedance z ohm and in every single pole
according to ieee std 56-1977 standard