Closed, Stopped and Unplugged Machine

CLOSED, STOPPED AND UNPLUGGED MACHINE

  • Measure partial discharge off-line

  • Measure insulation resistance i.r
    according to UQ602011C standard

  • Determine polarization index i.p.
    according to ieee std 43-2000 standard

  • Measure tangent of loss angle tan δ in winding insulation and its variation in δ tan δ
    based on voltage: 0.2 – 0.4 – 0.6 – 0.8 – rated voltage

  • Measure μf capacity of electrical windings respect to the mass,
    compared with same voltage present in the previous point

  • Test ground voltage
    according to UQ602010C standard

  • Test balance of phases through ohmic resistance
    according to UQ602012C standard

  • Test balance of phases through impedance z ohm
    according to ieee std 56-1977 standard

  • Internal check up through endoscopy with fiber optic lighting

  • Check up motor space heaters and thermoelements

 

ROTOR INSIDE STATOR

  • measure insulation resistance i.r
    according to UQ602011C standard

  • check total static ohm resistance
    according to UQ602012C standard

  • check total static z ohm impedance
    according to ieee std 56-1977 standard

 