Closed, Stopped and Unplugged Machine
CLOSED, STOPPED AND UNPLUGGED MACHINE
-
Measure partial discharge off-line
-
Measure insulation resistance i.r
according to UQ602011C standard -
Determine polarization index i.p.
according to ieee std 43-2000 standard -
Measure tangent of loss angle tan δ in winding insulation and its variation in δ tan δ
based on voltage: 0.2 – 0.4 – 0.6 – 0.8 – rated voltage -
Measure μf capacity of electrical windings respect to the mass,
compared with same voltage present in the previous point -
Test ground voltage
according to UQ602010C standard -
Test balance of phases through ohmic resistance
according to UQ602012C standard -
Test balance of phases through impedance z ohm
according to ieee std 56-1977 standard -
Internal check up through endoscopy with fiber optic lighting
-
Check up motor space heaters and thermoelements
ROTOR INSIDE STATOR
-
measure insulation resistance i.r
according to UQ602011C standard -
check total static ohm resistance
according to UQ602012C standard -
check total static z ohm impedance
according to ieee std 56-1977 standard